NAAC ENERGY CONTROLS (P) LIMITED
Home Page  
Company Profile  
Showroom  
    Power Factor Correction & Harmonic Filter
    Power Quality Management
    Active Comp. PF / Harmonic Filter System
PQ Scada Software
To inquire, Select Product/s & Click on

Product Code : NAAC-10

[Select]
Product Specification
PQSCADA Analysis Software:
  • Data acquisition from different devices and protocols
  • Different visualization options (graph, reports)
  • Unique analysis tools
  • Hierarchical structure allows ease-of-use
  • Distributed architecture for best performance & reliability
  • 3rd party connectivity
  • Modular design allows adding modules while system is up and running
PQSCADA Analysis Software & Specifications:
Comprehensive Web Serverfor Remote Monitoring
The integral web server allows comprehensive monitoring and control of the unit, with 3-level user privileges and 128-bit SSL cryptographic protocol. It includes tabular display screens, graphical display and remote control and configuration screens. By using an existing web browser, the inconvenience of installing dedicated software is avoided. Most operations can be performed via the web server interface; the screens are intuitive and easy to use. This means that monitoring, managing and analyzing network data can be performed using the web interface.

PQSCADA Power Quality Management Software (Enterprise Edition)
Innovative PQSCADA enterprise analysis software enables operators to view, control, analyze and monitor multiple measurements devices simultaneously. Data is accurately time-synchronized within sites and across sites.

The practically unlimited amount of data, collected from the M4400 devices, is processed and analyzed by using the PQSCADA software. The operator receives a comprehensive picture of graphical system trends and time synchronized power quality values from multiple devices on same screen for statusand anomaly source-propagation analysis.

The software's distributed architecture is scalable and allows easy management of countless local and remote measurement devices. The scalability scheme supports physical expansions and reflects the hierarchy of the components in the electrical grid.

The architecture is built on nodes, sites and enterprises:

Nodes are software components that directly control measurement devices for collection, storage, management and ultimate analysis of measurement data.

Nodes are grouped logically under sites which serve as entry points for various applications (internal and 3rd party) and provide a real-time picture of all connected points for management and configuration functions. Enterprises is the umbrella site that comprises all sites provides all-inclusive
snapshots of the network (trends and data).

Measurement:
  • Accuracy < 0.1%
  • Up to 1 ,024 samples per cycle
  • 11 channels: 4 voltages, 4 currents, 3 temperature indicators
  • Simultaneous 11 channel sampling at 250 kHz (4 micro see)
  • Cycle-by-Cycletrends for all RM S values and harmonics
  • Harmonics up to 511th, inter- and sub-harmonics
  • Accurate measurement even with presence of harmonics and at all measurement scale
  • Onboard auto temperature calibration provides high accuracy in all temperature range
  • Full scale readings l0x from nominal voltages and currents at high accuracies
Onboard Data Logging:
  • 1 + year, every cycle on board logging of all measurements at high accuracy
  • Patent-pending PQZip compression technology with typical 1000:1 compress ratio
  • Solid-state standard off-the-shelf compact flash storage, up to 8GB
Standard Compliance:
  • Standard compliance testing to EN 50160, and others
  • 2 simultaneous and parallel harmonic computations: IEC 61000-4-30 and cycle-by-cycle
  • Voltage flickering according to IEC 61000-4-15 and unique fast flicker compatible algorithm for real-time analysis
Connectivity:
  • 2 fast Ethernet ports (10/100 M bit) with Power over Ethernet (Po E) device and source
  • USB and RS-485 / 422 ports (2-and4-wires, up to 115,200 bps)
  • Conventional TCP / IP based data packaging protocol, provides communication fortraditional TCP/lP supported software
  • Comprehensive built-in web server for remote monitoring using standard web browser
  • Integral OPC server for seamless connection with SCADA systems
Mechnical Design and Expansion Options:
  • Unlimited number of remote displays can be connected to one M4400
  • Unlimited number of M4400 can be monitored by single remote display
  • No limitto the distance between the device and remote display
  • Rear mounting; optional DIN rail mount
  • Standard Compact Flash (CF) expansion slot
  • Hardware expansions bystackable optional modules
Power Supply:
  • 4 power supply sources with automatic seamless change-over
  • Versatile AC power and DC voltages
  • Power Over Ethernet (Po E) allows both reception and dispatch of power overthe Ethernet port
  • Upto 25 second ride-through at power loss
The M4000 series includes:
  • M4400 - Power Quality Data Centers
  • M4100 - Remote monitors/displays (optional)
  • PQSCADA - Central analysis software
Other Products
Life Line Series Detuned Catalogue
Life Line Series Detuned Catalogue
Energy Saving & Energy Management Software
Energy Saving & Energy Management Software
Life Line Series APFC Panel
Life Line Series APFC Panel
Energy Management
Energy Management
Harmonic System for Office
Harmonic System for Office
Harmonic System for Industries
Harmonic System for Industries
 
<< Back
CONTACT DETAILS
C-135 Hosiery Complex, Phase II (Extn.),Noida - 201305, Uttar Pradesh, India
Phone:91-120-4221631-34
Fax:91-120-4221635
Send Mail     
Key Personnel
Mr. Chander M. Kapoor (Director)
Mobile:+919811199085
  
Copyright © 2006 tradeindia.com. All Rights Reserved. Designed & Developed by